Use this integration to connect a ZenControl site to KODE OS. KODE OS discovers gateways, control gear, and application controllers, polls status, and receives live dim, scene, colour, and override events.Supported capabilities
- Discover devices and points
- Collect sensor data
- Receive WebSocket (live) data
- Write dim level, scene, colour temperature, and override
Prerequisites
- A ZenControl cloud account with API access
- The API URL, authorization URL, client ID, client secret, and user code
- The Live API enabled for the site
- KODE OS access to
Data Sources
Configure the connector in KODE OS
- Open
Data Sourcesfor your building. - Select
API Catalog, then search forZenControl. - Select
+ Add Datasource. - Complete the connector fields, then validate credentials so KODE OS can load sites.
Site ID shows the site name and stores the site identifier. KODE OS reuses a valid token and refreshes it before it expires.
Discover devices and points
After you save the connector, selectDiscover. Review the returned devices and points, then save the records you want in KODE OS.
Every device uses the lighting canonical type.
For more details, see the Discovery guide.
Devices and points
Gateway
A gateway is not polled. Its points arrive on the Live API gateway connection stream.ECG (control gear)
status is polled. The other points arrive as live events. arcLevel, scene, and override are writable. colourTemp is writable only when the gear supports colour control.
ECD (application controller)
Both points use a REST poll. A missing operating mode is collected as down.What data you get
Point history
REST polls refreshstatus and operatingMode. Live events refresh dim level, scene, colour temperature, override, and gateway connection. KODE OS stores arcLevel as a percent. A write converts that percent to a DALI arc level from 0 to 254.
Polling schedule
- Point history — Default polling: 15 minutes (min: 15 minutes, max: 1 hour)
Available actions
Write actions are available on the writable ECG points.colourTemp can be written only on gear discovered as colour control. Other gear does not accept the command.
Use cases
Once connected, you can:- See dim level and the latest scene on each control gear
- Check gateway and device connection status
- Set a scene, dim level, colour temperature, or timed override from KODE OS
Troubleshooting
Authentication or connection error
Authentication or connection error
Confirm the API URL, Auth URL, client ID, and client secret. A used, expired, or mismatched user code must be replaced before the first token can be issued.
No live events arriving
No live events arriving
Confirm that the Live API is enabled for the site and that the connector is up. Dim level, scene, colour temperature, and override arrive only over the WebSocket.
Discovery returns no devices
Discovery returns no devices
Confirm that the credentials can list the selected site. Run
Discover again after the connection test succeeds.Colour temperature write is rejected
Colour temperature write is rejected
Only colour-control gear has a writable
colourTemp point. Enter the value in Kelvin.