Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.
Cloud BMS provides a library of pre-configured FCU (Fan Coil Unit) functional testing workflows. Each workflow commands valves or the fan, reads sensor response, and scores pass or fail against thresholds.Use this page as a parameter and point-requirements lookup. For how FTT decides pass or fail on heating, see How FTT decides if a heater works. To run one heating test before you schedule a project, see Run a test on a single device.Select a tab to open the workflow you need.
Cooling
Fan operation
Heating w/ Fan Ops
Heating w/o Fan Ops
Cooling w/ Fan Ops
Cooling w/o Fan Ops
This workflow will test an FCU for its cooling operation.
First, we display the initial conditions of the equipment.
Then KODE performs precondition checks to ensure the equipment is ready to be tested.
Next we will stop heating by commanding the hot water valve to 0%.
Then we will stop cooling by commanding the chilled water valve to 0%.
Finally we will command the chilled water valve to 100% to start cooling.
Outcome: This test will check a FCU’s ability to deliver cooling when the valve is set to 100%.
Recommended schedule: Run weekly per floor. Run when new FCUs are installed and programmed.
Point requirements:
Device
Required points
FCU
FCU Fan % Cmd, FCU Occupancy Cmd, FCU Chilled Water Valve Command, FCU Hot Water Valve Command
AHU
Discharge Air Pressure
Required preconditions
FCU Occupancy = Occupied
FCU Fan Cmd% > 5%
Chiller Diff Pressure > 10 PSI
Variations: Heating and cooling workflows with and without fan operation appear later on this page.
Workflow overview
Test step
Workflow
1 Pre-condition Check
1. FCU is Occupied 2. FCU Fan Cmd% > 5% 3. Chiller Diff Pressure > 10 PSI
2 Stop Heating
1. Control: Cmd Hot Water Valve to 0% 2. Success:FCU DAT is below the threshold
3 Stop Cooling
1. Control: Cmd Cold Water Valve to 0% 2. Success:FCU DAT is greater than the threshold
4 Start Cooling
1. Control: Cmd Cold Water Valve to 100% 2. Success:FCU DAT is below the threshold
Tuning parameters
#
Parameter
Description
1
Chilled Water Valve Close Cmd
Value used to command the chilled water valve when stopping cooling
2
Stop Cooling DAT Threshold
The DAT must be greater than this value to confirm cooling has stopped
3
Hot Water Valve Close Cmd
Value used to command the hot water valve when stopping heating
4
Stop Heating DAT Threshold
The DAT must be less than this value to confirm heating has stopped
5
Chilled Water Valve Open Cmd
Value used to command the chilled water valve when starting cooling
6
Start Cooling DAT Threshold
The DAT must be less than this value to confirm cooling has started
7
FCU Fan Cmd % Low Limit
If the Fan Cmd % is less than this value, the test will automatically archive
8
Stabilization Time
How long in seconds should the program wait when one sequence finishes, before moving onto the next?
9
Min Sequence Duration
What is the minimum length of time in seconds that a sequence should take to execute?
10
Max Sequence Duration
What is the maximum length of time in seconds that a sequence should take to execute?
If you need assistance with interpreting your results, reach out to the support team at support@kodelabs.com.
Testing procedure
Pre-conditions check
Before testing is started, it must be verified that the FCU is running.Verify that device is Occupied.
If this condition is not met, STOP the workflow and ARCHIVE.
Setup testing conditions
In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.Stop Active HeatingWeight: 1/3
Verify that discharge temperature is within 5△°F [Heating - Delta] above mixed temperature
Stop Active CoolingWeight: 1/3
Verify that discharge temperature is within 5△°F [Cooling - Delta] below mixed temperature
Test the Fan
It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.Test 1: Stop the FanWeight: 1/3
Command the fan to OFF
Pass if Fan Speed is reports to be less than 5% [Fan Max Threshold]
Test 2: Start the Fan
Command the fan to ON
Pass: Fan Percentage >= 10% [Fan Min Threshold]
Parameters
Display
Hint
Stop Fan Weight [1]
Weight on the overall test assigned to this sequence. All sequences sum up their weights and each weight is divided by this total.
Fan Stop Command [%]
To what percentage do we want to test the stopping operation
Heating Stop Command [%]
To what percentage do we want to test the closing operation
Stop Heating Weight [1]
Weight on the overall test assigned to this sequence
Stop Cooling Weight [1]
Weight on the overall test assigned to this sequence
Fan Start Command [100%]
To what percentage do we want to test the starting operation
Cooling Delta [5△°F]
The threshold tolerance for cooling. Delta between ZT and DAT.
Fan Max Threshold [5%]
The maximum threshold (%) for a fan off status
Fan Min Threshold [10%]
The minimum threshold (%) for a fan on status
Reaction Time [240sec]
How long to wait for the actuators to fully do their job
Stabilization Time [60sec]
How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled
Measure After [60sec]
How long to wait in seconds to start checking the feedback readings
Heating Delta [5△°F]
The threshold tolerance for heating. Delta between ZT and DAT.
Fan Current Max Threshold [0.2Amp]
The maximum amps threshold for a fan off status
Fan Current Min Threshold [0.3Amp]
The minimum amps threshold for a fan on status
DAT Cooling Arb Threshold [19°F]
The DAT below which there would be indication of cooling
Testing procedure
Pre-conditions check
Before testing is started, it must be verified that the FCU is running.Verify that device is Occupied.
If this condition is not met, STOP the workflow and ARCHIVE.
Setup testing conditions
In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.Stop Active HeatingWeight: 1/7
Verify that discharge temperature is within 5△°F [Heating - Delta] above mixed temperature
Stop Active Cooling
Verify that discharge temperature is within 5△°F [Cooling - Delta] below mixed temperature
Test the Fan
It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.Test 1: Stop the FanWeight: 1/7
Command the fan to OFF
Pass if Fan Speed is reports to be less than 5% [Fan Max Threshold]
Test 2: Start the FanWeight: 1/7
Command the fan to ON
Pass: Fan Percentage >= 10% [Fan Min Threshold]
Test Heating
Test 3: Start Heating OperationWeight: 4/7
Command Heating to ON
Pass if zone temp raised by at least 5△°F [Heating - Delta] OR
Pass if discharge temp is greater than 28°F [DAT Heating Arb Threshold]
Parameters
Display
Hint
Stop Fan Weight [1]
Weight on the overall test assigned to this sequence
Fan Stop Command [%]
To what percentage do we want to test the stopping operation
Start Heating Weight [4]
Weight on the overall test assigned to this sequence
Heating Start Command [100%]
To what percentage do we want to test the opening operation
Heating Stop Command [%]
To what percentage do we want to test the closing operation
Stop Heating Weight [1]
Weight on the overall test assigned to this sequence
Cooling Stop Command [%]
To what percentage do we want to test the closing operation
Start Fan Weight [1]
Weight on the overall test assigned to this sequence
Fan Start Command [100%]
To what percentage do we want to test the starting operation
Cooling Delta [5△°F]
The threshold tolerance for cooling. Delta between ZT and DAT.
Fan Max Threshold [5%]
The maximum threshold (%) for a fan off status
Fan Min Threshold [10%]
The minimum threshold (%) for a fan on status
Reaction Time [240sec]
How long to wait for the actuators to fully do their job
Stabilization Time [60sec]
How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled
Measure After [60sec]
How long to wait in seconds to start checking the feedback readings
Heating Delta [5△°F]
The threshold tolerance for heating. Delta between ZT and DAT.
DAT Heating Arb Threshold [28°F]
The DAT above which there would be indication of heating
Fan Current Max Threshold [0.2Amp]
The maximum amps threshold for a fan off status
Fan Current Min Threshold [0.3Amp]
The minimum amps threshold for a fan on status
Testing procedure
Pre-conditions check
Before testing is started, it must be verified that the FCU is running.Verify that device is Occupied.
If this condition is not met, STOP the workflow and ARCHIVE.
Setup testing conditions
In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.Stop Active HeatingWeight: 1/6
Verify that discharge temperature is within 5△°F [Heating - Delta] above mixed temperature
Stop Active CoolingWeight: 1/6
Verify that discharge temperature is within 5△°F [Cooling - Delta] below mixed temperature
Test Heating
Test 3: Start Heating OperationWeight: 4/6
Command Heating to ON
Pass if zone temp raised by at least 5△°F [Heating - Delta] OR
Pass if discharge temp is greater than 28°F [DAT Heating Arb Threshold]
Parameters
Display
Hint
Heating Start Command [100%]
To what percentage do we want to test the opening operation
Start Heating Weight [4]
Weight on the overall test assigned to this sequence
Heating Stop Command [%]
To what percentage do we want to test the closing operation
Stop Heating Weight [1]
Weight on the overall test assigned to this sequence
Stop Cooling Weight [1]
Weight on the overall test assigned to this sequence
Cooling Stop Command [%]
To what percentage do we want to test the closing operation
Cooling Delta [5△°F]
The threshold tolerance for cooling. Delta between ZT and DAT.
Fan Max Threshold [5%]
The maximum threshold (%) for a fan off status
Fan Min Threshold [10%]
The minimum threshold (%) for a fan on status
Reaction Time [240sec]
How long to wait for the actuators to fully do their job
Stabilization Time [60sec]
How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled
Measure After [60sec]
How long to wait in seconds to start checking the feedback readings
Heating Delta [5△°F]
The threshold tolerance for heating. Delta between ZT and DAT.
DAT Heating Arb Threshold [28°F]
The DAT above which there would be indication of heating
Fan Current Max Threshold [0.5Amp]
The maximum threshold (Amps) for a fan off status
Fan Current Min Threshold [1Amp]
The minimum threshold (Amps) for a fan on status
Testing procedure
Pre-conditions check
Before testing is started, it must be verified that the FCU is running.Verify that device is Occupied.
If this condition is not met, STOP the workflow and ARCHIVE.
Setup testing conditions
In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.Stop Active HeatingWeight: 4/11
Verify that discharge temperature is within 5△°F [Heating - Delta] above mixed temperature
Stop Active CoolingWeight: 1/11
Verify that discharge temperature is within 5△°F [Cooling - Delta] below mixed temperature
Test the Fan
It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.Test 1: Stop the FanWeight: 1/11
Command the fan to OFF
Pass if Fan Speed is reports to be less than 5% [Fan Max Threshold]
Test 2: Start the FanWeight: 1/11
Command the fan to ON
Pass: Fan Percentage >= 10% [Fan Min Threshold]
Test Cooling
Test 3: Start Cooling OperationWeight: 4/11
Command Cooling to ON
Pass if zone temp dropped by at least 5△°F [Cooling - Delta] OR
Pass if discharge temp is less than 19°F [DAT Cooling Arb Threshold]
Parameters
Display
Hint
Stop Fan Weight [1]
Weight on the overall test assigned to this sequence
Fan Stop Command [%]
To what percentage do we want to test the stopping operation
Heating Stop Command [%]
To what percentage do we want to test the closing operation
Stop Heating Weight [4]
Weight on the overall test assigned to this sequence
Stop Cooling Weight [1]
Weight on the overall test assigned to this sequence
Cooling Stop Command [%]
To what percentage do we want to test the closing operation
Start Fan Weight [1]
Weight on the overall test assigned to this sequence
Fan Start Command [100%]
To what percentage do we want to test the starting operation
Cooling Delta [5△°F]
The threshold tolerance for cooling. Delta between ZT and DAT.
Fan Max Threshold [5%]
The maximum threshold (%) for a fan off status
Fan Min Threshold [10%]
The minimum threshold (%) for a fan on status
Reaction Time [240sec]
How long to wait for the actuators to fully do their job
Stabilization Time [60sec]
How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled
Measure After [60sec]
How long to wait in seconds to start checking the feedback readings
Heating Delta [5△°F]
The threshold tolerance for heating. Delta between ZT and DAT.
DAT Cooling Arb Threshold [19°F]
The DAT below which there would be indication of cooling
Fan Current Max Threshold [0.2Amp]
The maximum amps threshold for a fan off status
Fan Current Min Threshold [0.3Amp]
The minimum amps threshold for a fan on status
Cooling Start Command [100%]
To what percentage do we want to test the opening operation
Start Cooling Weight [4]
Weight on the overall test assigned to this sequence
Testing procedure
Pre-conditions check
Before testing is started, it must be verified that the FCU is running.Verify that device is Occupied.
If this condition is not met, STOP the workflow and ARCHIVE.
Setup testing conditions
In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.Stop Active HeatingWeight: 4/9
Verify that discharge temperature is within 5△°F [Heating - Delta] above mixed temperature
Stop Active CoolingWeight: 1/9
Verify that discharge temperature is within 5△°F [Cooling - Delta] below mixed temperature
Test Cooling
Test: Start Cooling OperationWeight: 4/9
Command Cooling to ON
Pass if zone temp dropped by at least 5△°F [Cooling - Delta] OR
Pass if discharge temp is less than 16°F [DAT Cooling Arb Threshold]
Parameters
Display
Hint
Heating Stop Command [%]
To what percentage do we want to test the closing operation
Stop Heating Weight [4]
Weight on the overall test assigned to this sequence
Stop Cooling Weight [1]
Weight on the overall test assigned to this sequence
Cooling Stop Command [%]
To what percentage do we want to test the closing operation
Cooling Delta [5△°F]
The threshold tolerance for cooling. Delta between ZT and DAT.
Fan Max Threshold [5%]
The maximum threshold (%) for a fan off status
Fan Min Threshold [10%]
The minimum threshold (%) for a fan on status
Reaction Time [240sec]
How long to wait for the actuators to fully do their job
Stabilization Time [60sec]
How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled
Measure After [60sec]
How long to wait in seconds to start checking the feedback readings
Heating Delta [5△°F]
The threshold tolerance for heating. Delta between ZT and DAT.
DAT Cooling Arb Threshold [16°F]
The DAT below which there would be indication of cooling
Fan Current Min Threshold [1Amp]
The minimum threshold (Amps) for a fan on status
Fan Current Max Threshold [0.5Amp]
The maximum threshold (Amps) for a fan off status
Cooling Start Command [100%]
To what percentage do we want to test the opening operation
Start Cooling Weight [4]
Weight on the overall test assigned to this sequence
Next steps
Run a single-device test
Run an on-demand FCU heating test and read the score.
VAV workflows
Explore the VAV workflow library for damper, heating, and airflow tracking tests.
AHU workflows
Explore the AHU workflow library for damper, heating, cooling, and VFD tests.
FTT projects
Assign workflows to devices and schedule automated testing.
Last modified on October 20, 2026
Was this page helpful?
{"docsConfig":{"theme":"aspen","$schema":"https://mintlify.com/docs.json","name":"KODE Labs - Product Documentation","colors":{"primary":"#015BFA","light":"#3A9AFF","dark":"#015BFA"},"logo":{"light":"https://mintcdn.com/kodelabs/YfYud6Al4TM68wc2/logo/logo-light.png?fit=max\u0026auto=format\u0026n=YfYud6Al4TM68wc2\u0026q=85\u0026s=00d4ffd6ad7a592e52856804d1a53d12","dark":"https://mintcdn.com/kodelabs/YfYud6Al4TM68wc2/logo/logo-dark.png?fit=max\u0026auto=format\u0026n=YfYud6Al4TM68wc2\u0026q=85\u0026s=a6769f53904d96f5a53ea0c4b3c972d6","href":"/"},"favicon":{"light":"https://mintcdn.com/kodelabs/H3HEEQdnaG21O57-/logo/favicon-light.png?fit=max\u0026auto=format\u0026n=H3HEEQdnaG21O57-\u0026q=85\u0026s=3ae881e353dfb5c2f667e175ec82c799","dark":"https://mintcdn.com/kodelabs/H3HEEQdnaG21O57-/logo/favicon-dark.png?fit=max\u0026auto=format\u0026n=H3HEEQdnaG21O57-\u0026q=85\u0026s=845431bc7d53ce5bf50f56ef53d9137f"},"api":{"params":{"expanded":"closed"},"playground":{"display":"interactive","proxy":true},"examples":{"defaults":"required","languages":["bash","javascript","python","powershell"],"prefill":true,"autogenerate":true},"url":"full"},"appearance":{"default":"light","strict":true},"background":{"color":{"light":"#ffffff","dark":"#121212"}},"navbar":{"links":[{"href":"https://kodelabs.com/contact/","label":"Contact Us"}]},"footer":{"socials":{"x":"https://twitter.com/kodelabs","instagram":"https://www.instagram.com/kode_labs","linkedin":"https://www.linkedin.com/company/kodelabs","youtube":"https://www.youtube.com/channel/UCKCnsgnYtugWxMPzu3UEHkw"},"links":[{"header":"Platform","items":[{"label":"KODE OS","href":"https://kodelabs.com"},{"label":"Integrations","href":"https://kodelabs.com/partners/integrations-library"},{"label":"Security","href":"https://kodelabs.com/security"}]},{"header":"Resources","items":[{"label":"Blog","href":"https://kodelabs.com/blog"},{"label":"Reports \u0026 Guides","href":"https://kodelabs.com/resources"},{"label":"Podcasts \u0026 Webinars","href":"https://kodelabs.com/resources"},{"label":"Case Studies","href":"https://kodelabs.com/case-studies"},{"label":"News","href":"https://kodelabs.com/news"}]},{"header":"Solutions","items":[{"label":"Commercial","href":"https://kodelabs.com/solutions/commercial-real-estate"},{"label":"Corporate","href":"https://kodelabs.com/solutions/corporate"},{"label":"Retail","href":"https://kodelabs.com/solutions/retail"},{"label":"Healthcare","href":"https://kodelabs.com/solutions/healthcare"},{"label":"Education","href":"https://kodelabs.com/solutions/education"}]},{"header":"Company","items":[{"label":"About","href":"https://kodelabs.com/about"},{"label":"Careers","href":"https://kodelabs.com/careers"},{"label":"Internships","href":"https://kodelabs.com/internships"},{"label":"Contact Us","href":"https://kodelabs.com/contact"}]}]},"search":{"prompt":"Search our docs..."},"fonts":{"heading":{"family":"Manrope","weight":600},"body":{"family":"Inter"}},"icons":{"library":"lucide"},"styling":{"eyebrows":"section","codeblocks":{"theme":{"light":"github-light","dark":"github-dark"}},"latex":false},"integrations":{"ga4":{"measurementId":"G-WKYQEE1T4B"}},"banner":{"content":"KODE 3.20 is live. See [what's new in November 2026](/whats-new/2026/v3.20-november-2026).","dismissible":true,"color":{"light":"#015BFA","dark":"#015BFA"}},"errors":{"404":{"redirect":false,"title":"We're working on it!","description":"If you're not seeing this page, we're definitely updating it."}},"contextual":{"options":["copy","view",{"title":"Email KODE support","description":"Contact KODE Labs support for help","icon":"mail","href":"mailto:support@kodelabs.com"}],"display":"toc"},"interaction":{"drilldown":false},"metadata":{"timestamp":true},"navigation":{"global":{"anchors":[{"anchor":"Home","icon":"house","href":"/"},{"anchor":"What's New","icon":"megaphone","href":"/whats-new/2026/v3.20-november-2026"}]},"pages":[]}},"deployment":{"deploymentMetadataValue":{"subdomain":"kodelabs","hasAudioNarration":false,"actualSubdomain":"kodelabs","customDomains":["docs.kodelabs.com"],"gitSource":{"type":"github","owner":"kode-labs","repo":"docs","deployBranch":"main","contentDirectory":"","isPrivate":true,"mountPath":"","label":""},"feedback":{"thumbs":true,"agentFeedback":true},"entitlements":{"AI_CHAT":{"status":"ENABLED"},"REMOVE_BRANDING":{"status":"ENABLED"},"CONTEXTUAL_FEEDBACK":{"status":"ENABLED"},"CODE_SNIPPET_FEEDBACK":{"status":"ENABLED"},"WEB_MCP":{"status":"ENABLED"},"NARRATION":{"status":"ENABLED"}},"buildId":"6af8e4f300819710da52c87a","clientVersion":"0.0.4227","searchFilterCounts":[{"language":"default","tag":"Integrations","count":214},{"language":"default","tag":"All Integrations","count":205},{"language":"default","tag":"KODE API","count":143},{"language":"default","tag":"API reference","count":132},{"language":"default","tag":"EnerG","count":61},{"language":"default","tag":"Meters","count":37},{"language":"default","tag":"Building BI","count":35},{"language":"default","tag":"AssetOps","count":32},{"language":"default","tag":"Cloud BMS","count":31},{"language":"default","tag":"Reference","count":29}],"searchSettings":{"showContentSnippets":true,"isFiltersEnabled":true,"maxResults":10}},"assistantConfig":{"enableStarterQuestions":true,"enableContextualStarterQuestions":true},"basePath":"","hasChatPermissions":true,"hasWebMcpPermissions":true,"toggles":[],"googleFontsInlined":true},"customCss":[{"filePath":"custom.css","href":"/_mintlify/custom/kodelabs/fd6257d3326e3afa/custom.css"}]}
{"page":{"pagePath":"products/ftt/fcu-workflows","slug":"/products/ftt/fcu-workflows","pageMetadata":{"title":"FCU workflow library","sidebarTitle":"FCU workflows","description":"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.","icon":"thermometer","keywords":["FTT","FCU","workflows","fan operation","heating","cooling","functional testing","Cloud BMS"],"href":"/products/ftt/fcu-workflows"},"description":{"compiledSource":"\"use strict\";\nconst {jsx: _jsx} = arguments[0];\nconst {useMDXComponents: _provideComponents} = arguments[0];\nfunction _createMdxContent(props) {\n const _components = {\n p: \"p\",\n ..._provideComponents(),\n ...props.components\n };\n return _jsx(_components.p, {\n children: \"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.\"\n });\n}\nfunction MDXContent(props = {}) {\n const {wrapper: MDXLayout} = {\n ..._provideComponents(),\n ...props.components\n };\n return MDXLayout ? _jsx(MDXLayout, {\n ...props,\n children: _jsx(_createMdxContent, {\n ...props\n })\n }) : _createMdxContent(props);\n}\nreturn {\n default: MDXContent\n};\n","frontmatter":{},"scope":{}},"pageType":"default","mdx":{"mdxSource":{"compiledSource":"\"use strict\";const{Fragment:_Fragment,jsx:_jsx,jsxs:_jsxs}=arguments[0];const{useMDXComponents:_provideComponents}=arguments[0];function _createMdxContent(props){const _components={a:`a`,code:`code`,em:`em`,hr:`hr`,li:`li`,ol:`ol`,p:`p`,strong:`strong`,tbody:`tbody`,td:`td`,th:`th`,thead:`thead`,tr:`tr`,ul:`ul`,..._provideComponents(),...props.components},{Card,CardGroup,Check,Heading,Info,Note,Tab,Table,Tabs,Tip,Warning}=_components;if(!Card)_missingMdxReference(`Card`,true);if(!CardGroup)_missingMdxReference(`CardGroup`,true);if(!Check)_missingMdxReference(`Check`,true);if(!Heading)_missingMdxReference(`Heading`,true);if(!Info)_missingMdxReference(`Info`,true);if(!Note)_missingMdxReference(`Note`,true);if(!Tab)_missingMdxReference(`Tab`,true);if(!Table)_missingMdxReference(`Table`,true);if(!Tabs)_missingMdxReference(`Tabs`,true);if(!Tip)_missingMdxReference(`Tip`,true);if(!Warning)_missingMdxReference(`Warning`,true);return _jsxs(_Fragment,{children:[_jsx(_components.p,{children:`Cloud BMS provides a library of pre-configured FCU (Fan Coil Unit) functional testing workflows. Each workflow commands valves or the fan, reads sensor response, and scores pass or fail against thresholds.`}),`\n`,_jsxs(_components.p,{children:[`Use this page as a parameter and point-requirements lookup. For how FTT decides pass or fail on heating, see `,_jsx(_components.a,{href:`/products/ftt/overview#example-how-ftt-decides-if-a-heater-works`,children:`How FTT decides if a heater works`}),`. To run one heating test before you schedule a project, see `,_jsx(_components.a,{href:`/products/ftt/test-results#run-a-test-on-a-single-device`,children:`Run a test on a single device`}),`.`]}),`\n`,_jsx(_components.p,{children:`Select a tab to open the workflow you need.`}),`\n`,_jsx(_components.hr,{}),`\n`,_jsxs(Tabs,{children:[_jsxs(Tab,{title:`Cooling`,icon:`snowflake`,id:`cooling`,\"data-child-heading-ids\":`[\"required-preconditions\",\"workflow-overview\",\"tuning-parameters\"]`,children:[_jsx(_components.p,{children:_jsx(_components.em,{children:`This workflow will test an FCU for its cooling operation.`})}),_jsxs(_components.ol,{children:[`\n`,_jsx(_components.li,{children:`First, we display the initial conditions of the equipment.`}),`\n`,_jsx(_components.li,{children:`Then KODE performs precondition checks to ensure the equipment is ready to be tested.`}),`\n`,_jsx(_components.li,{children:`Next we will stop heating by commanding the hot water valve to 0%.`}),`\n`,_jsx(_components.li,{children:`Then we will stop cooling by commanding the chilled water valve to 0%.`}),`\n`,_jsx(_components.li,{children:`Finally we will command the chilled water valve to 100% to start cooling.`}),`\n`]}),_jsx(Check,{children:_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Outcome:`}),` This test will check a FCU’s ability to deliver cooling when the valve is set to 100%.`]})}),_jsx(Tip,{children:_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Recommended schedule:`}),` Run weekly per floor. Run when new FCUs are installed and programmed.`]})}),_jsxs(Info,{children:[_jsx(_components.p,{children:_jsx(_components.strong,{children:`Point requirements:`})}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Device`}),_jsx(_components.th,{children:`Required points`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsx(_components.td,{children:`FCU`}),_jsx(_components.td,{children:`FCU Fan % Cmd, FCU Occupancy Cmd, FCU Chilled Water Valve Command, FCU Hot Water Valve Command`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{children:`AHU`}),_jsx(_components.td,{children:`Discharge Air Pressure`})]})]})]})]}),_jsx(Heading,{level:`3`,id:`required-preconditions`,children:`Required preconditions`}),_jsxs(_components.ol,{children:[`\n`,_jsxs(_components.li,{children:[_jsx(_components.em,{children:`FCU Occupancy`}),` = `,_jsx(_components.code,{children:`Occupied`})]}),`\n`,_jsxs(_components.li,{children:[_jsx(_components.em,{children:`FCU Fan Cmd%`}),` > `,_jsx(_components.code,{children:`5%`})]}),`\n`,_jsxs(_components.li,{children:[_jsx(_components.em,{children:`Chiller Diff Pressure`}),` > `,_jsx(_components.code,{children:`10 PSI`})]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Variations:`}),` Heating and cooling workflows with and without fan operation appear later on this page.`]}),_jsx(Heading,{level:`3`,id:`workflow-overview`,children:`Workflow overview`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Test step`}),_jsx(_components.th,{children:`Workflow`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsx(_components.td,{children:_jsx(_components.strong,{children:`1 Pre-condition Check`})}),_jsxs(_components.td,{children:[`1. FCU is `,_jsx(_components.code,{children:`Occupied`}),` 2. `,_jsx(_components.em,{children:`FCU Fan Cmd%`}),` > `,_jsx(_components.code,{children:`5%`}),` 3. `,_jsx(_components.em,{children:`Chiller Diff Pressure`}),` > `,_jsx(_components.code,{children:`10 PSI`})]})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{children:_jsx(_components.strong,{children:`2 Stop Heating`})}),_jsxs(_components.td,{children:[`1. `,_jsx(_components.strong,{children:`Control:`}),` Cmd Hot Water Valve to `,_jsx(_components.code,{children:`0%`}),` 2. `,_jsx(_components.strong,{children:`Success:`}),` `,_jsx(_components.em,{children:`FCU DAT`}),` is below the threshold`]})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{children:_jsx(_components.strong,{children:`3 Stop Cooling`})}),_jsxs(_components.td,{children:[`1. `,_jsx(_components.strong,{children:`Control:`}),` Cmd Cold Water Valve to `,_jsx(_components.code,{children:`0%`}),` 2. `,_jsx(_components.strong,{children:`Success:`}),` `,_jsx(_components.em,{children:`FCU DAT`}),` is greater than the threshold`]})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{children:_jsx(_components.strong,{children:`4 Start Cooling`})}),_jsxs(_components.td,{children:[`1. `,_jsx(_components.strong,{children:`Control:`}),` Cmd Cold Water Valve to `,_jsx(_components.code,{children:`100%`}),` 2. `,_jsx(_components.strong,{children:`Success:`}),` `,_jsx(_components.em,{children:`FCU DAT`}),` is below the threshold`]})]})]})]}),_jsx(Heading,{level:`3`,id:`tuning-parameters`,children:`Tuning parameters`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`#`}),_jsx(_components.th,{children:`Parameter`}),_jsx(_components.th,{children:`Description`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`1`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Chilled Water Valve Close Cmd`})}),_jsx(_components.td,{children:`Value used to command the chilled water valve when stopping cooling`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`2`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Stop Cooling DAT Threshold`})}),_jsx(_components.td,{children:`The DAT must be greater than this value to confirm cooling has stopped`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`3`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Hot Water Valve Close Cmd`})}),_jsx(_components.td,{children:`Value used to command the hot water valve when stopping heating`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`4`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Stop Heating DAT Threshold`})}),_jsx(_components.td,{children:`The DAT must be less than this value to confirm heating has stopped`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`5`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Chilled Water Valve Open Cmd`})}),_jsx(_components.td,{children:`Value used to command the chilled water valve when starting cooling`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`6`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Start Cooling DAT Threshold`})}),_jsx(_components.td,{children:`The DAT must be less than this value to confirm cooling has started`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`7`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`FCU Fan Cmd % Low Limit`})}),_jsx(_components.td,{children:`If the Fan Cmd % is less than this value, the test will automatically archive`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`8`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Stabilization Time`})}),_jsx(_components.td,{children:`How long in seconds should the program wait when one sequence finishes, before moving onto the next?`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`9`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Min Sequence Duration`})}),_jsx(_components.td,{children:`What is the minimum length of time in seconds that a sequence should take to execute?`})]}),_jsxs(_components.tr,{children:[_jsx(_components.td,{\"data-numeric\":`true`,children:`10`}),_jsx(_components.td,{children:_jsx(_components.code,{children:`Max Sequence Duration`})}),_jsx(_components.td,{children:`What is the maximum length of time in seconds that a sequence should take to execute?`})]})]})]}),_jsx(Note,{children:_jsxs(_components.p,{children:[`If you need assistance with interpreting your results, reach out to the support team at `,_jsx(_components.a,{href:`mailto:support@kodelabs.com`,children:`support@kodelabs.com`}),`.`]})}),_jsx(_components.hr,{})]}),_jsxs(Tab,{title:`Fan operation`,icon:`fan`,id:`fan-operation`,\"data-child-heading-ids\":`[\"testing-procedure\",\"pre-conditions-check\",\"setup-testing-conditions\",\"test-the-fan\",\"parameters\"]`,children:[_jsx(Heading,{level:`3`,id:`testing-procedure`,children:`Testing procedure`}),_jsx(Heading,{level:`3`,id:`pre-conditions-check`,children:`Pre-conditions check`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`Before testing is started, it must be verified that the FCU is running.`})}),_jsx(_components.p,{children:_jsxs(_components.strong,{children:[`Verify that device is `,_jsx(_components.code,{children:`Occupied`}),`.`]})}),_jsx(Warning,{children:_jsx(_components.p,{children:`If this condition is not met, STOP the workflow and ARCHIVE.`})}),_jsx(Heading,{level:`3`,id:`setup-testing-conditions`,children:`Setup testing conditions`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Heating`}),` `,_jsx(_components.em,{children:`Weight: 1/3`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] above `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Cooling`}),` `,_jsx(_components.em,{children:`Weight: 1/3`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] below `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-the-fan`,children:`Test the Fan`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 1: Stop the Fan`}),` `,_jsx(_components.em,{children:`Weight: 1/3`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command the fan to `,_jsx(_components.code,{children:`OFF`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`Fan Speed`}),` is reports to be less than `,_jsx(_components.code,{children:`5%`}),` [Fan Max Threshold]`]}),`\n`]}),_jsx(_components.p,{children:_jsx(_components.strong,{children:`Test 2: Start the Fan`})}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command the fan to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass: `,_jsx(_components.em,{children:`Fan Percentage`}),` >= `,_jsx(_components.code,{children:`10%`}),` [Fan Min Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`parameters`,children:`Parameters`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Display`}),_jsx(_components.th,{children:`Hint`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Fan Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence. All sequences sum up their weights and each weight is divided by this total.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the stopping operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Heating Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Cooling Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the starting operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for cooling. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Max Threshold`}),` [5%]`]}),_jsx(_components.td,{children:`The maximum threshold (%) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Min Threshold`}),` [10%]`]}),_jsx(_components.td,{children:`The minimum threshold (%) for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Reaction Time`}),` [240sec]`]}),_jsx(_components.td,{children:`How long to wait for the actuators to fully do their job`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stabilization Time`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Measure After`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait in seconds to start checking the feedback readings`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for heating. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Max Threshold`}),` [0.2Amp]`]}),_jsx(_components.td,{children:`The maximum amps threshold for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Min Threshold`}),` [0.3Amp]`]}),_jsx(_components.td,{children:`The minimum amps threshold for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`DAT Cooling Arb Threshold`}),` [19°F]`]}),_jsx(_components.td,{children:`The DAT below which there would be indication of cooling`})]})]})]}),_jsx(_components.hr,{})]}),_jsxs(Tab,{title:`Heating w/ Fan Ops`,icon:`flame`,id:`heating-w%2F-fan-ops`,\"data-child-heading-ids\":`[\"testing-procedure-2\",\"pre-conditions-check-2\",\"setup-testing-conditions-2\",\"test-the-fan-2\",\"test-heating\",\"parameters-2\"]`,children:[_jsx(Heading,{level:`3`,id:`testing-procedure-2`,children:`Testing procedure`}),_jsx(Heading,{level:`3`,id:`pre-conditions-check-2`,children:`Pre-conditions check`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`Before testing is started, it must be verified that the FCU is running.`})}),_jsx(_components.p,{children:_jsxs(_components.strong,{children:[`Verify that device is `,_jsx(_components.code,{children:`Occupied`}),`.`]})}),_jsx(Warning,{children:_jsx(_components.p,{children:`If this condition is not met, STOP the workflow and ARCHIVE.`})}),_jsx(Heading,{level:`3`,id:`setup-testing-conditions-2`,children:`Setup testing conditions`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Heating`}),` `,_jsx(_components.em,{children:`Weight: 1/7`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] above `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsx(_components.p,{children:_jsx(_components.strong,{children:`Stop Active Cooling`})}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] below `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-the-fan-2`,children:`Test the Fan`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 1: Stop the Fan`}),` `,_jsx(_components.em,{children:`Weight: 1/7`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command the fan to `,_jsx(_components.code,{children:`OFF`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`Fan Speed`}),` is reports to be less than `,_jsx(_components.code,{children:`5%`}),` [Fan Max Threshold]`]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 2: Start the Fan`}),` `,_jsx(_components.em,{children:`Weight: 1/7`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command the fan to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass: `,_jsx(_components.em,{children:`Fan Percentage`}),` >= `,_jsx(_components.code,{children:`10%`}),` [Fan Min Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-heating`,children:`Test Heating`}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 3: Start Heating Operation`}),` `,_jsx(_components.em,{children:`Weight: 4/7`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command Heating to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`zone temp`}),` raised by at least `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] OR`]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`discharge temp`}),` is greater than `,_jsx(_components.code,{children:`28°F`}),` [DAT Heating Arb Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`parameters-2`,children:`Parameters`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Display`}),_jsx(_components.th,{children:`Hint`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Fan Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the stopping operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Start Heating Weight`}),` [4]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the opening operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Heating Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Start Fan Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the starting operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for cooling. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Max Threshold`}),` [5%]`]}),_jsx(_components.td,{children:`The maximum threshold (%) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Min Threshold`}),` [10%]`]}),_jsx(_components.td,{children:`The minimum threshold (%) for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Reaction Time`}),` [240sec]`]}),_jsx(_components.td,{children:`How long to wait for the actuators to fully do their job`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stabilization Time`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Measure After`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait in seconds to start checking the feedback readings`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for heating. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`DAT Heating Arb Threshold`}),` [28°F]`]}),_jsx(_components.td,{children:`The DAT above which there would be indication of heating`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Max Threshold`}),` [0.2Amp]`]}),_jsx(_components.td,{children:`The maximum amps threshold for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Min Threshold`}),` [0.3Amp]`]}),_jsx(_components.td,{children:`The minimum amps threshold for a fan on status`})]})]})]}),_jsx(_components.hr,{})]}),_jsxs(Tab,{title:`Heating w/o Fan Ops`,icon:`thermometer`,id:`heating-w%2Fo-fan-ops`,\"data-child-heading-ids\":`[\"testing-procedure-3\",\"pre-conditions-check-3\",\"setup-testing-conditions-3\",\"test-heating-2\",\"parameters-3\"]`,children:[_jsx(Heading,{level:`3`,id:`testing-procedure-3`,children:`Testing procedure`}),_jsx(Heading,{level:`3`,id:`pre-conditions-check-3`,children:`Pre-conditions check`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`Before testing is started, it must be verified that the FCU is running.`})}),_jsx(_components.p,{children:_jsxs(_components.strong,{children:[`Verify that device is `,_jsx(_components.code,{children:`Occupied`}),`.`]})}),_jsx(Warning,{children:_jsx(_components.p,{children:`If this condition is not met, STOP the workflow and ARCHIVE.`})}),_jsx(Heading,{level:`3`,id:`setup-testing-conditions-3`,children:`Setup testing conditions`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Heating`}),` `,_jsx(_components.em,{children:`Weight: 1/6`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] above `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Cooling`}),` `,_jsx(_components.em,{children:`Weight: 1/6`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] below `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-heating-2`,children:`Test Heating`}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 3: Start Heating Operation`}),` `,_jsx(_components.em,{children:`Weight: 4/6`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command Heating to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`zone temp`}),` raised by at least `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] OR`]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`discharge temp`}),` is greater than `,_jsx(_components.code,{children:`28°F`}),` [DAT Heating Arb Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`parameters-3`,children:`Parameters`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Display`}),_jsx(_components.th,{children:`Hint`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the opening operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Start Heating Weight`}),` [4]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Heating Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Cooling Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for cooling. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Max Threshold`}),` [5%]`]}),_jsx(_components.td,{children:`The maximum threshold (%) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Min Threshold`}),` [10%]`]}),_jsx(_components.td,{children:`The minimum threshold (%) for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Reaction Time`}),` [240sec]`]}),_jsx(_components.td,{children:`How long to wait for the actuators to fully do their job`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stabilization Time`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Measure After`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait in seconds to start checking the feedback readings`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for heating. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`DAT Heating Arb Threshold`}),` [28°F]`]}),_jsx(_components.td,{children:`The DAT above which there would be indication of heating`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Max Threshold`}),` [0.5Amp]`]}),_jsx(_components.td,{children:`The maximum threshold (Amps) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Min Threshold`}),` [1Amp]`]}),_jsx(_components.td,{children:`The minimum threshold (Amps) for a fan on status`})]})]})]}),_jsx(_components.hr,{})]}),_jsxs(Tab,{title:`Cooling w/ Fan Ops`,icon:`wind`,id:`cooling-w%2F-fan-ops`,\"data-child-heading-ids\":`[\"testing-procedure-4\",\"pre-conditions-check-4\",\"setup-testing-conditions-4\",\"test-the-fan-3\",\"test-cooling\",\"parameters-4\"]`,children:[_jsx(Heading,{level:`3`,id:`testing-procedure-4`,children:`Testing procedure`}),_jsx(Heading,{level:`3`,id:`pre-conditions-check-4`,children:`Pre-conditions check`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`Before testing is started, it must be verified that the FCU is running.`})}),_jsx(_components.p,{children:_jsxs(_components.strong,{children:[`Verify that device is `,_jsx(_components.code,{children:`Occupied`}),`.`]})}),_jsx(Warning,{children:_jsx(_components.p,{children:`If this condition is not met, STOP the workflow and ARCHIVE.`})}),_jsx(Heading,{level:`3`,id:`setup-testing-conditions-4`,children:`Setup testing conditions`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Heating`}),` `,_jsx(_components.em,{children:`Weight: 4/11`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] above `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Cooling`}),` `,_jsx(_components.em,{children:`Weight: 1/11`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] below `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-the-fan-3`,children:`Test the Fan`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`It must also be verified that the fan can successfully be commanded to start and stop. If either of these conditions are not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 1: Stop the Fan`}),` `,_jsx(_components.em,{children:`Weight: 1/11`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command the fan to `,_jsx(_components.code,{children:`OFF`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`Fan Speed`}),` is reports to be less than `,_jsx(_components.code,{children:`5%`}),` [Fan Max Threshold]`]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 2: Start the Fan`}),` `,_jsx(_components.em,{children:`Weight: 1/11`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command the fan to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass: `,_jsx(_components.em,{children:`Fan Percentage`}),` >= `,_jsx(_components.code,{children:`10%`}),` [Fan Min Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-cooling`,children:`Test Cooling`}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test 3: Start Cooling Operation`}),` `,_jsx(_components.em,{children:`Weight: 4/11`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command Cooling to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`zone temp`}),` dropped by at least `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] OR`]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`discharge temp`}),` is less than `,_jsx(_components.code,{children:`19°F`}),` [DAT Cooling Arb Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`parameters-4`,children:`Parameters`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Display`}),_jsx(_components.th,{children:`Hint`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Fan Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the stopping operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Heating Weight`}),` [4]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Cooling Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Start Fan Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the starting operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for cooling. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Max Threshold`}),` [5%]`]}),_jsx(_components.td,{children:`The maximum threshold (%) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Min Threshold`}),` [10%]`]}),_jsx(_components.td,{children:`The minimum threshold (%) for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Reaction Time`}),` [240sec]`]}),_jsx(_components.td,{children:`How long to wait for the actuators to fully do their job`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stabilization Time`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Measure After`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait in seconds to start checking the feedback readings`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for heating. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`DAT Cooling Arb Threshold`}),` [19°F]`]}),_jsx(_components.td,{children:`The DAT below which there would be indication of cooling`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Max Threshold`}),` [0.2Amp]`]}),_jsx(_components.td,{children:`The maximum amps threshold for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Min Threshold`}),` [0.3Amp]`]}),_jsx(_components.td,{children:`The minimum amps threshold for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the opening operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Start Cooling Weight`}),` [4]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]})]})]}),_jsx(_components.hr,{})]}),_jsxs(Tab,{title:`Cooling w/o Fan Ops`,icon:`droplets`,id:`cooling-w%2Fo-fan-ops`,\"data-child-heading-ids\":`[\"testing-procedure-5\",\"pre-conditions-check-5\",\"setup-testing-conditions-5\",\"test-cooling-2\",\"parameters-5\"]`,children:[_jsx(Heading,{level:`3`,id:`testing-procedure-5`,children:`Testing procedure`}),_jsx(Heading,{level:`3`,id:`pre-conditions-check-5`,children:`Pre-conditions check`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`Before testing is started, it must be verified that the FCU is running.`})}),_jsx(_components.p,{children:_jsxs(_components.strong,{children:[`Verify that device is `,_jsx(_components.code,{children:`Occupied`}),`.`]})}),_jsx(Warning,{children:_jsx(_components.p,{children:`If this condition is not met, STOP the workflow and ARCHIVE.`})}),_jsx(Heading,{level:`3`,id:`setup-testing-conditions-5`,children:`Setup testing conditions`}),_jsx(_components.p,{children:_jsx(_components.em,{children:`In order to ensure that testing is accurate, outside sources of heating and cooling need to be eliminated or minimized. If any of these conditions are applicable and not verified, then the testing will be aborted.`})}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Heating`}),` `,_jsx(_components.em,{children:`Weight: 4/9`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Heating - Delta] above `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Stop Active Cooling`}),` `,_jsx(_components.em,{children:`Weight: 1/9`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Verify that `,_jsx(_components.em,{children:`discharge temperature`}),` is within `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] below `,_jsx(_components.em,{children:`mixed temperature`})]}),`\n`]}),_jsx(Heading,{level:`3`,id:`test-cooling-2`,children:`Test Cooling`}),_jsxs(_components.p,{children:[_jsx(_components.strong,{children:`Test: Start Cooling Operation`}),` `,_jsx(_components.em,{children:`Weight: 4/9`})]}),_jsxs(_components.ul,{children:[`\n`,_jsxs(_components.li,{children:[`Command Cooling to `,_jsx(_components.code,{children:`ON`})]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`zone temp`}),` dropped by at least `,_jsx(_components.code,{children:`5△°F`}),` [Cooling - Delta] OR`]}),`\n`,_jsxs(_components.li,{children:[`Pass if `,_jsx(_components.em,{children:`discharge temp`}),` is less than `,_jsx(_components.code,{children:`16°F`}),` [DAT Cooling Arb Threshold]`]}),`\n`]}),_jsx(Heading,{level:`3`,id:`parameters-5`,children:`Parameters`}),_jsxs(Table,{children:[_jsx(_components.thead,{children:_jsxs(_components.tr,{children:[_jsx(_components.th,{children:`Display`}),_jsx(_components.th,{children:`Hint`})]})}),_jsxs(_components.tbody,{children:[_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Heating Weight`}),` [4]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stop Cooling Weight`}),` [1]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Stop Command`}),` [%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the closing operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for cooling. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Max Threshold`}),` [5%]`]}),_jsx(_components.td,{children:`The maximum threshold (%) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Min Threshold`}),` [10%]`]}),_jsx(_components.td,{children:`The minimum threshold (%) for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Reaction Time`}),` [240sec]`]}),_jsx(_components.td,{children:`How long to wait for the actuators to fully do their job`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Stabilization Time`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait for the system to come to stability after an actuator command and the conditions have been fulfilled`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Measure After`}),` [60sec]`]}),_jsx(_components.td,{children:`How long to wait in seconds to start checking the feedback readings`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Heating Delta`}),` [5△°F]`]}),_jsx(_components.td,{children:`The threshold tolerance for heating. Delta between ZT and DAT.`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`DAT Cooling Arb Threshold`}),` [16°F]`]}),_jsx(_components.td,{children:`The DAT below which there would be indication of cooling`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Min Threshold`}),` [1Amp]`]}),_jsx(_components.td,{children:`The minimum threshold (Amps) for a fan on status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Fan Current Max Threshold`}),` [0.5Amp]`]}),_jsx(_components.td,{children:`The maximum threshold (Amps) for a fan off status`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Cooling Start Command`}),` [100%]`]}),_jsx(_components.td,{children:`To what percentage do we want to test the opening operation`})]}),_jsxs(_components.tr,{children:[_jsxs(_components.td,{children:[_jsx(_components.code,{children:`Start Cooling Weight`}),` [4]`]}),_jsx(_components.td,{children:`Weight on the overall test assigned to this sequence`})]})]})]})]})]}),`\n`,_jsx(Heading,{level:`2`,id:`next-steps`,children:`Next steps`}),`\n`,_jsxs(CardGroup,{cols:2,children:[_jsx(Card,{title:`Run a single-device test`,icon:`play`,href:`/products/ftt/test-results#run-a-test-on-a-single-device`,arrow:true,children:_jsx(_components.p,{children:`Run an on-demand FCU heating test and read the score.`})}),_jsx(Card,{title:`VAV workflows`,icon:`fan`,href:`/products/ftt/vav-workflows`,arrow:true,children:_jsx(_components.p,{children:`Explore the VAV workflow library for damper, heating, and airflow tracking tests.`})}),_jsx(Card,{title:`AHU workflows`,icon:`wind`,href:`/products/ftt/ahu-workflows`,arrow:true,children:_jsx(_components.p,{children:`Explore the AHU workflow library for damper, heating, cooling, and VFD tests.`})}),_jsx(Card,{title:`FTT projects`,icon:`folder-kanban`,href:`/products/ftt/projects`,arrow:true,children:_jsx(_components.p,{children:`Assign workflows to devices and schedule automated testing.`})})]})]})}function MDXContent(props={}){const{wrapper:MDXLayout}={..._provideComponents(),...props.components};return MDXLayout?_jsx(MDXLayout,{...props,children:_jsx(_createMdxContent,{...props})}):_createMdxContent(props)}return{default:MDXContent};function _missingMdxReference(id,component){throw new Error(`Expected `+(component?`component`:`object`)+\" `\"+id+\"` to be defined: you likely forgot to import, pass, or provide it.\")}","frontmatter":{},"scope":{"codeStyling":{"theme":{"light":"github-light","dark":"github-dark"}},"config":{},"pageMetadata":{"title":"FCU workflow library","sidebarTitle":"FCU workflows","description":"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.","icon":"thermometer","keywords":["FTT","FCU","workflows","fan operation","heating","cooling","functional testing","Cloud BMS"],"href":"/products/ftt/fcu-workflows"}}},"mdxSourceWithNoJs":null},"mdxExtracts":{"tableOfContents":[{"title":"Required preconditions","slug":"required-preconditions","depth":3,"children":[],"tabId":"cooling"},{"title":"Workflow overview","slug":"workflow-overview","depth":3,"children":[],"tabId":"cooling"},{"title":"Tuning parameters","slug":"tuning-parameters","depth":3,"children":[],"tabId":"cooling"},{"title":"Testing procedure","slug":"testing-procedure","depth":3,"children":[],"tabId":"fan-operation"},{"title":"Pre-conditions check","slug":"pre-conditions-check","depth":3,"children":[],"tabId":"fan-operation"},{"title":"Setup testing conditions","slug":"setup-testing-conditions","depth":3,"children":[],"tabId":"fan-operation"},{"title":"Test the Fan","slug":"test-the-fan","depth":3,"children":[],"tabId":"fan-operation"},{"title":"Parameters","slug":"parameters","depth":3,"children":[],"tabId":"fan-operation"},{"title":"Testing procedure","slug":"testing-procedure-2","depth":3,"children":[],"tabId":"heating-w%2F-fan-ops"},{"title":"Pre-conditions check","slug":"pre-conditions-check-2","depth":3,"children":[],"tabId":"heating-w%2F-fan-ops"},{"title":"Setup testing conditions","slug":"setup-testing-conditions-2","depth":3,"children":[],"tabId":"heating-w%2F-fan-ops"},{"title":"Test the Fan","slug":"test-the-fan-2","depth":3,"children":[],"tabId":"heating-w%2F-fan-ops"},{"title":"Test Heating","slug":"test-heating","depth":3,"children":[],"tabId":"heating-w%2F-fan-ops"},{"title":"Parameters","slug":"parameters-2","depth":3,"children":[],"tabId":"heating-w%2F-fan-ops"},{"title":"Testing procedure","slug":"testing-procedure-3","depth":3,"children":[],"tabId":"heating-w%2Fo-fan-ops"},{"title":"Pre-conditions check","slug":"pre-conditions-check-3","depth":3,"children":[],"tabId":"heating-w%2Fo-fan-ops"},{"title":"Setup testing conditions","slug":"setup-testing-conditions-3","depth":3,"children":[],"tabId":"heating-w%2Fo-fan-ops"},{"title":"Test Heating","slug":"test-heating-2","depth":3,"children":[],"tabId":"heating-w%2Fo-fan-ops"},{"title":"Parameters","slug":"parameters-3","depth":3,"children":[],"tabId":"heating-w%2Fo-fan-ops"},{"title":"Testing procedure","slug":"testing-procedure-4","depth":3,"children":[],"tabId":"cooling-w%2F-fan-ops"},{"title":"Pre-conditions check","slug":"pre-conditions-check-4","depth":3,"children":[],"tabId":"cooling-w%2F-fan-ops"},{"title":"Setup testing conditions","slug":"setup-testing-conditions-4","depth":3,"children":[],"tabId":"cooling-w%2F-fan-ops"},{"title":"Test the Fan","slug":"test-the-fan-3","depth":3,"children":[],"tabId":"cooling-w%2F-fan-ops"},{"title":"Test Cooling","slug":"test-cooling","depth":3,"children":[],"tabId":"cooling-w%2F-fan-ops"},{"title":"Parameters","slug":"parameters-4","depth":3,"children":[],"tabId":"cooling-w%2F-fan-ops"},{"title":"Testing procedure","slug":"testing-procedure-5","depth":3,"children":[],"tabId":"cooling-w%2Fo-fan-ops"},{"title":"Pre-conditions check","slug":"pre-conditions-check-5","depth":3,"children":[],"tabId":"cooling-w%2Fo-fan-ops"},{"title":"Setup testing conditions","slug":"setup-testing-conditions-5","depth":3,"children":[],"tabId":"cooling-w%2Fo-fan-ops"},{"title":"Test Cooling","slug":"test-cooling-2","depth":3,"children":[],"tabId":"cooling-w%2Fo-fan-ops"},{"title":"Parameters","slug":"parameters-5","depth":3,"children":[],"tabId":"cooling-w%2Fo-fan-ops"},{"title":"Next steps","slug":"next-steps","depth":2,"children":[]}],"codeExamples":{}},"jsLinks":["/_mintlify/custom/kodelabs/ce5d3bd08e955b7b/navbar-assistant.js"],"subdomain":"kodelabs","siteName":"KODE Labs - Product Documentation","title":"FCU workflow library - KODE Labs - Product Documentation","contextualStarterQuestions":[{"_id":"6ad7cd3b46ba2bb8df34e942","deploymentId":"67fd4d9635f314f3a994be65","questionText":"How do I test cooling operation?","status":"active","generatedBy":"contextual","path":"products/ftt/fcu-workflows","createdAt":"2026-10-20T20:21:15.574Z","updatedAt":"2026-10-20T20:21:15.574Z","__v":0},{"_id":"6ad7cd3b46ba2bb8df34e941","deploymentId":"67fd4d9635f314f3a994be65","questionText":"What FCU points are required?","status":"active","generatedBy":"contextual","path":"products/ftt/fcu-workflows","createdAt":"2026-10-20T20:21:15.574Z","updatedAt":"2026-10-20T20:21:15.574Z","__v":0},{"_id":"6ad7cd3b46ba2bb8df34e943","deploymentId":"67fd4d9635f314f3a994be65","questionText":"When should I run these tests?","status":"active","generatedBy":"contextual","path":"products/ftt/fcu-workflows","createdAt":"2026-10-20T20:21:15.574Z","updatedAt":"2026-10-20T20:21:15.574Z","__v":0}],"navMaps":{"firstHrefInVersion":{},"firstHrefInLanguage":{}},"lastModified":"2026-10-20T20:20:52.080Z","gitLastModified":"2026-10-20T20:20:04.000Z","originalFileLocation":"products/ftt/fcu-workflows.mdx"},"headHtml":"\u003cscript data-mint-head>(function(){var d=document.documentElement,p=\"light\";if(!p){try{p=localStorage.getItem(\"isDarkMode\")}catch(e){}if(p==='true')p='dark';else if(p==='false')p='light';if(p!=='light'\u0026\u0026p!=='dark'\u0026\u0026p!=='system')p=\"light\"}var r=p==='system'?(matchMedia(\"(prefers-color-scheme: dark)\").matches?'dark':'light'):p;d.classList.remove(r==='dark'?'light':'dark');d.classList.add(r);d.setAttribute(\"data-theme-preference\",p)})();\u003c/script>\u003cmeta data-mint-head name=\"description\" content=\"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.\">\u003cmeta data-mint-head name=\"application-name\" content=\"KODE Labs - Product Documentation\">\u003cmeta data-mint-head name=\"generator\" content=\"Mintlify\">\u003clink data-mint-head rel=\"icon\" type=\"image/png\" sizes=\"192x192\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon/android-chrome-192x192.png\" media=\"(prefers-color-scheme: light)\">\u003clink data-mint-head rel=\"apple-touch-icon\" type=\"image/png\" sizes=\"180x180\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon/apple-touch-icon.png\">\u003clink data-mint-head rel=\"icon\" type=\"image/png\" sizes=\"16x16\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon/favicon-16x16.png\" media=\"(prefers-color-scheme: light)\">\u003clink data-mint-head rel=\"icon\" type=\"image/png\" sizes=\"32x32\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon/favicon-32x32.png\" media=\"(prefers-color-scheme: light)\">\u003clink data-mint-head rel=\"shortcut icon\" type=\"image/x-icon\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon/favicon.ico\" media=\"(prefers-color-scheme: light)\">\u003clink data-mint-head rel=\"icon\" type=\"image/png\" sizes=\"192x192\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon-dark/android-chrome-192x192.png\" media=\"(prefers-color-scheme: dark)\">\u003clink data-mint-head rel=\"icon\" type=\"image/png\" sizes=\"16x16\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon-dark/favicon-16x16.png\" media=\"(prefers-color-scheme: dark)\">\u003clink data-mint-head rel=\"icon\" type=\"image/png\" sizes=\"32x32\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon-dark/favicon-32x32.png\" media=\"(prefers-color-scheme: dark)\">\u003clink data-mint-head rel=\"shortcut icon\" type=\"image/x-icon\" href=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon-dark/favicon.ico\" media=\"(prefers-color-scheme: dark)\">\u003cmeta data-mint-head property=\"og:title\" content=\"FCU workflow library - KODE Labs - Product Documentation\">\u003cmeta data-mint-head property=\"og:description\" content=\"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.\">\u003cmeta data-mint-head property=\"og:site_name\" content=\"KODE Labs - Product Documentation\">\u003cmeta data-mint-head property=\"og:url\" content=\"https://docs.kodelabs.com/products/ftt/fcu-workflows\">\u003cmeta data-mint-head property=\"og:type\" content=\"website\">\u003cmeta data-mint-head property=\"og:image\" content=\"https://kodelabs.mintlify.site/_mintlify/api/og/v2?division=Workflow+library\u0026amp;title=FCU+workflow+library\u0026amp;description=Reference+for+all+FCU+functional+testing+workflows+including+fan+operation%2C+heating+and+cooling+tests+with+and+without+fan+verification%2C+and+FCU+cooling+operati\u0026amp;theme=ac252318c016362b89abdbd3\u0026amp;signature=46f0da89a97dbe83c9e04b964a8f66f7d74481145caa2e7cc5377446a742307e\">\u003cmeta data-mint-head property=\"og:image:width\" content=\"1200\">\u003cmeta data-mint-head property=\"og:image:height\" content=\"630\">\u003cmeta data-mint-head name=\"twitter:card\" content=\"summary_large_image\">\u003cmeta data-mint-head name=\"twitter:title\" content=\"FCU workflow library - KODE Labs - Product Documentation\">\u003cmeta data-mint-head name=\"twitter:description\" content=\"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.\">\u003cmeta data-mint-head name=\"twitter:image\" content=\"https://kodelabs.mintlify.site/_mintlify/api/og/v2?division=Workflow+library\u0026amp;title=FCU+workflow+library\u0026amp;description=Reference+for+all+FCU+functional+testing+workflows+including+fan+operation%2C+heating+and+cooling+tests+with+and+without+fan+verification%2C+and+FCU+cooling+operati\u0026amp;theme=ac252318c016362b89abdbd3\u0026amp;signature=46f0da89a97dbe83c9e04b964a8f66f7d74481145caa2e7cc5377446a742307e\">\u003cmeta data-mint-head name=\"twitter:image:width\" content=\"1200\">\u003cmeta data-mint-head name=\"twitter:image:height\" content=\"630\">\u003cmeta data-mint-head name=\"msapplication-config\" content=\"/mintlify-assets/_mintlify/favicons/kodelabs/vtcGE1gj2AkAE1l2/_generated/favicon/browserconfig.xml\">\u003cmeta data-mint-head name=\"apple-mobile-web-app-title\" content=\"KODE Labs - Product Documentation\">\u003cmeta data-mint-head name=\"msapplication-TileColor\" content=\"#015BFA\">\u003clink data-mint-head rel=\"canonical\" href=\"https://docs.kodelabs.com/products/ftt/fcu-workflows\">\u003clink data-mint-head rel=\"alternate\" type=\"application/xml\" href=\"/sitemap.xml\">\u003clink data-mint-head rel=\"alternate\" type=\"text/markdown\" href=\"/products/ftt/fcu-workflows.md\">\u003cscript data-mint-head type=\"application/ld+json\">{\"@context\":\"https://schema.org\",\"@graph\":[{\"@type\":\"Organization\",\"@id\":\"https://docs.kodelabs.com/#organization\",\"name\":\"KODE Labs - Product Documentation\",\"url\":\"https://docs.kodelabs.com\",\"logo\":{\"@type\":\"ImageObject\",\"url\":\"https://mintcdn.com/kodelabs/YfYud6Al4TM68wc2/logo/logo-light.png?fit=max\u0026auto=format\u0026n=YfYud6Al4TM68wc2\u0026q=85\u0026s=00d4ffd6ad7a592e52856804d1a53d12\"}},{\"@type\":\"WebSite\",\"@id\":\"https://docs.kodelabs.com#website\",\"name\":\"KODE Labs - Product Documentation\",\"url\":\"https://docs.kodelabs.com\",\"publisher\":{\"@id\":\"https://docs.kodelabs.com/#organization\"}},{\"@type\":\"WebPage\",\"@id\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows#webpage\",\"url\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows\",\"name\":\"FCU workflow library\",\"description\":\"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.\",\"dateModified\":\"2026-10-20T20:20:04.000Z\",\"isPartOf\":{\"@id\":\"https://docs.kodelabs.com#website\"},\"breadcrumb\":{\"@id\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows#breadcrumb\"}},{\"@type\":\"BreadcrumbList\",\"@id\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Workflows\",\"item\":\"https://docs.kodelabs.com/products/ftt/workflows\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Workflow library\",\"item\":\"https://docs.kodelabs.com/products/ftt/vav-workflows\"},{\"@type\":\"ListItem\",\"position\":3,\"name\":\"FCU workflow library\",\"item\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows\"}]},{\"@type\":[\"Article\",\"TechArticle\"],\"@id\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows#article\",\"headline\":\"FCU workflow library\",\"name\":\"FCU workflow library\",\"description\":\"Reference for all FCU functional testing workflows including fan operation, heating and cooling tests with and without fan verification, and FCU cooling operation.\",\"url\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows\",\"mainEntityOfPage\":{\"@id\":\"https://docs.kodelabs.com/products/ftt/fcu-workflows#webpage\"},\"dateModified\":\"2026-10-20T20:20:04.000Z\",\"keywords\":\"FTT, FCU, workflows, fan operation, heating, cooling, functional testing, Cloud BMS\",\"publisher\":{\"@id\":\"https://docs.kodelabs.com/#organization\"},\"isPartOf\":{\"@id\":\"https://docs.kodelabs.com#website\"}}]}\u003c/script>","agentPointerHref":"/products/ftt/fcu-workflows.md","siteName":"KODE Labs - Product Documentation","nav":{"global":{"anchors":[{"anchor":"Home","icon":"house","href":"/"},{"anchor":"What's New","icon":"megaphone","href":"/whats-new/2026/v3.20-november-2026"}]},"products":[{"product":"Cloud BMS","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/cloud-bms.svg","description":"Cloud building management, graphics, and control","pages":[{"title":"Cloud BMS","href":"/products/kode-os/get-started/introduction"}]},{"product":"Building BI","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/bbi.svg","description":"Dashboards and analytics for building performance","pages":[{"title":"Building BI","href":"/products/building-bi/overview"}]},{"product":"FDD","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/fdd.svg","description":"Fault detection and diagnostics for equipment","pages":[{"title":"FDD","href":"/products/fdd/overview"}]},{"product":"FTT","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/ftt.svg","description":"Automated functional testing and commissioning","groups":[{"group":"Get Started","pages":[{"title":"What is Functional Testing?","sidebarTitle":"Introduction","icon":"rocket","href":"/products/ftt/overview"}]},{"group":"Testing","pages":[{"title":"Test results","sidebarTitle":"Test results","icon":"list-checks","href":"/products/ftt/test-results"},{"title":"FTT projects","sidebarTitle":"Projects","icon":"clipboard-list","href":"/products/ftt/projects"}]},{"group":"Workflows","pages":[{"title":"Workflows","sidebarTitle":"Workflows","icon":"workflow","href":"/products/ftt/workflows"},{"title":"Workflow logic blocks","sidebarTitle":"Logic blocks","icon":"puzzle","href":"/products/ftt/workflow-logic-blocks"},{"title":"Workflow creator guide","sidebarTitle":"Creator guide","icon":"drafting-compass","href":"/products/ftt/workflow-creator-guide"},{"group":"Workflow library","icon":"library","expanded":false,"pages":[{"title":"VAV workflow library","sidebarTitle":"VAV workflows","description":"Reference for all VAV functional testing workflows including damper min/max, induced heating, airflow setpoint tracking, damper operation, heating operation, and induce heating/cooling checks.","icon":"fan","href":"/products/ftt/vav-workflows"},{"title":"FCU workflow library","sidebarTitle":"FCU workflows","icon":"thermometer","href":"/products/ftt/fcu-workflows"},{"title":"AHU workflows","sidebarTitle":"AHU workflows","description":"Reference for all AHU functional testing workflows including cooling operation, heating operation, mixed damper operation, and VFD operation tests.","icon":"wind","href":"/products/ftt/ahu-workflows"},{"title":"Heat pump workflow library","sidebarTitle":"HP workflows","icon":"flame","href":"/products/ftt/hp-workflows"}]}]},{"group":"Deployment","pages":[{"title":"Deployment guide","sidebarTitle":"Deployment","icon":"rocket","href":"/products/ftt/deployment"}]},{"group":"Reference","icon":"book-a","pages":[{"title":"KODE glossary","sidebarTitle":"Glossary","icon":"book-a","href":"/products/ftt/glossary"}]}]},{"product":"AssetOps","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/assetops.svg","description":"Asset and maintenance operations","pages":[{"title":"AssetOps","href":"/products/assetops/quickstart/overview"}]},{"product":"EnerG","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/enerG.svg","description":"Energy management and sustainability reporting","pages":[{"title":"EnerG","href":"/products/energ/get-started/introduction"}]},{"product":"Launchpad","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/launchpad.svg","description":"Dynamic management for apps, users, and buildings","pages":[{"title":"Launchpad","href":"/products/launchpad/get-started/introduction"}]},{"product":"Mobile app","icon":"https://mintlify.s3.us-west-1.amazonaws.com/kodelabs/images/mobile-app.svg","description":"Monitor and operate buildings from iOS and Android","pages":[{"title":"Mobile app","href":"/products/mobile-app/overview"}]},{"product":"KODE API","icon":"braces","description":"Build services and integrations with KODE OS","pages":[{"title":"KODE API","href":"/products/kode-api"}]},{"product":"Integrations","icon":"cable","description":"Connect 200+ building systems to KODE OS","pages":[{"title":"Integrations","href":"/products/integrations/get-started/introduction"}]},{"product":"What's New","icon":"megaphone","description":"KODE platform release notes and updates","pages":[{"title":"What's New","href":"/whats-new/2026/v3.20-november-2026"}]}]},"basePath":"","title":"FCU workflow library - KODE Labs - Product Documentation","deploymentId":"dpl_vSEmv961Ncyvz1psVwgUnTXQMSYk","buildId":"dpl_vSEmv961Ncyvz1psVwgUnTXQMSYk","dynamics":["10e4515597"],"chunks":["BannerMarkdown-DnSAhvaM.js","dist-DIfYWxfm.js","lib-DMeTj1gb.js","lib-B8HbPgcC.js","katex-Dbtb6Wk7.js","html-void-elements-mCSPHezU.js","marked.esm-CZWythHk.js"]}